MANUAL FOR ALARMS AND INFORMATION MESSAGES

GOLD RX/PX/CX/SD

Generation F

Applicable to Program Version 1.30 and newer versions

Related Manuals for Swegon GOLD RX

Summary of Contents for Swegon GOLD RX

  • Page 1
    MANUAL FOR ALARMS AND INFORMATION MESSAGES GOLD RX/PX/CX/SD Generation F Applicable to Program Version 1.30 and newer versions…
  • Page 2
    GB.GOLDSKFLARM.190920 Content Innehåll 1. Alarm Descriptions with Factory Settings ….. 3 2. Information Messages ………. 35 The document was originally written in Swedish. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 3: Alarm Descriptions With Factory Settings

    3 second alarm delay. PRE-HEAT, VALVE MONITORING TRIPPED 10 m Valve actuator, air heater, water. The valve actuator’s response signal deviates from the outgoing control signal. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 4
    EXTRA REGULATION SEQUENCE 1, TEMPERATURE PRO- TECTION FROM COMMUNICATION ERROR The air handling unit’s control unit does receive the temperature via the external communications interface within the set time limit. 5 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 5: Electrical Heater

    SOR DEFECTIVE Supply flow temperature sensor to the combi coil is defective or not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module F. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 6
    Xzone, SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE Supply air sensor is defective or is not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module A. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 7: Alarm Limit

    20 second alarm delay. Xzone, COOL, ALARM INPUT 2 TRIPPED 20 s Alarm input 2 Xzone cool has tripped. Check terminal connections 19-20 on I/O-module B. 20 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 8
    “Sensor 3” (the sensor placed on the left-hand side) or “Sensor 4” (the sensor placed on the right-hand side). For GOLD RX the sensor can also be used as a tem- perature alarm and be placed after the supply air fan. 3 second alarm delay.
  • Page 9
    B = B alarm h=hour 10:4 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY COMPENSATION DEFECTIVE (GOLD RX/PX/CX) The temperature sensor in the extract air fan intake cannot establish correct communications or shows an incorrect value. Check that the sensor is connected to the connection on the IQlogic controller.
  • Page 10
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 11
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 12
    20 minutes. Alarm limit 5 K (adjustable). Check the correct function on heat exchangers and any reheaters. Also check that the aforementioned are dimensioned for the current setpoint. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 13
    The heat exchanger’s efficiency is below the preset alarm limit for more than 2 minutes. Check the operation of the heat exchanger. GOLD RX: check that the heat exchanger belts do not slip. GOLD PX: check damper operations so that all dampers and actuators work correctly.
  • Page 14
    The VOC sensor has read a level below or above the set point alarm limit for more than 60 seconds. Factory setting 450 ppm and 10,000 ppm (adjustable). Alarm group 14: Spare www.swegon.com We reserve the right to alter specifications without notice.
  • Page 15
    Check that the function selector switch on the I/O mod- ule is set to position 3 and that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 16
    Check terminal connections 2(Y) and 4(U) on I/O-mod- ule 3. Check that the damper does not seize or that the actua- tor slips on the damper shaft. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 17
    Check that the sensor is connected with the right polar- ity. For pump run at constant speed: Check terminal connections 7-8 on I/O-module 1. Check that the sensor is connected with the right polar- ity. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 18
    The air handling unit’s control unit cannot establish cor- rect communications with the rotary heat exchanger’s motor controller. Check that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 19
    Check the incoming voltage to the air handling unit and the outgoing voltage from the transformer. The voltage must not exceed 36 V +15 %. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 20: Over Temperature

    ALARM LIMIT 5) Heated water temperature exceeds preset set point longer than 30 minutes. Alarm limit 7 K (adjustable). Check the correct function on heating circuit and that the valve functions correctly. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 21
    COOL DX, COMPRESSOR NO. 1 LOW PRESSURE SEN- SOR DEFECTIVE Low pressure sensor is defective or is not connected. Check terminal connections 8 (Black), 15 (Green) and 16 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 22
    COOL DX, COMPRESSOR NO. 2 HIGH PRESSURE SEN- SOR DEFECTIVE High pressure sensor is defective or is not connected. Check terminal connections 2 (Black), 9 (Green) and 10 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 23
    The air handling unit’s control unit cannot establish cor- rect communication with I/O module no. 5, AQUA Link 23:11 AQUA Link, PUMP MONITORING TRIPPED 10 s Pump to AQUA Link is defective. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 24: Communication Error

    27:2 AHU FILTER, SUPPLY AIR FOULED 10 m The pressure across the AHU supply air filter has ex- ceeded the preset alarm limit for more than 10 minutes. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 25
    AIRFLOW MEASUREMENT, PURGING PRESSURE SENSOR 10 s NO. B COMMUNICATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with the sensor of the rotary heat exchanger purging sector. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 26
    , OUTDOOR AIR DAMPER MONITORING TRIPPED 10 m The damper actuator does not move to the right posi- tion. The position-confirming output signal from the damper is not the same as the input control signal. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 27
    A new service period can be set and reset under ALARM SETTINGS. 33:15 LOCK FUNCTION TRIPPED – – – Contact Swegon or their representative. Alarm group 34: External controls 34:1 EXTERNAL CONTROL, I/O MODULE NO. 3 COMMUNI- 10 s CATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with I/O module No.
  • Page 28
    682, 697 563, 578, MIRU NO. 1-3 FLOW BELOW SET POINT ALARM LIMIT 1200 s 40:8 The flow has dropped below its set point for a period longer than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 29
    EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR 10 s 60:1 841, 856, The air handling unit’s control unit cannot establish 871, 886 correct communication with the extract air fan motor controller. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 30
    EXTRACT AIR FAN NO. 1A I/O MODULE COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with extract air fan no. 1A I/O module. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 31
    Phase sequence protection for feed voltage to HC has tripped. 71:1 1051 HC COMPRESSOR MOTOR CONTROL COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with the HC compressor motor control. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 32
    HC pressure equalisation high pressure circuit 1, has tripped. 72:14 1079 HC LOW PRESSURE CIRCUIT 1 BELOW ALARM LIMIT 10 s HC low pressure circuit 1 falls below the set alarm limit. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 33
    1206, SMART LINK NO. 1-4 EVAPORATION TEMPERATURE 30 s 84:6 1221, BELOW ALARM LIMIT 1236, The evaporation temperature drops below the preset 1251 alarm limit for more than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 34
    Stops the AHU if the temperature is below the adjustable limit. Inactive as factory setting. Contact Swegon or their representative. Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU Control 4.
  • Page 35: Information Messages

    ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent at 30 minute intervals. The message is not received after completed heat exchanger calibration. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 36: Calibration Failure

    Temperature sensor for heat-retaining function is not fitted or is not connected correctly. 99:14 INTERNAL SERIAL MEMORY ERROR CPEx1 Internal serial memory error CPEx1 99:15 CLOCK CIRCUIT DEFECTIVE Circuit for the clock is defective www.swegon.com We reserve the right to alter specifications without notice.

  • Bookmarks

Quick Links

MANUAL FOR ALARMS AND INFORMATION MESSAGES

GOLD RX/PX/CX/SD

Generation F

Applicable to Program Version 1.30 and newer versions

Related Manuals for Swegon GOLD RX

Summary of Contents for Swegon GOLD RX

  • Page 1
    MANUAL FOR ALARMS AND INFORMATION MESSAGES GOLD RX/PX/CX/SD Generation F Applicable to Program Version 1.30 and newer versions…
  • Page 2
    GB.GOLDSKFLARM.190920 Content Innehåll 1. Alarm Descriptions with Factory Settings ….. 3 2. Information Messages ………. 35 The document was originally written in Swedish. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 3: Alarm Descriptions With Factory Settings

    3 second alarm delay. PRE-HEAT, VALVE MONITORING TRIPPED 10 m Valve actuator, air heater, water. The valve actuator’s response signal deviates from the outgoing control signal. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 4
    EXTRA REGULATION SEQUENCE 1, TEMPERATURE PRO- TECTION FROM COMMUNICATION ERROR The air handling unit’s control unit does receive the temperature via the external communications interface within the set time limit. 5 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 5: Electrical Heater

    SOR DEFECTIVE Supply flow temperature sensor to the combi coil is defective or not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module F. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 6
    Xzone, SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE Supply air sensor is defective or is not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module A. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 7: Alarm Limit

    20 second alarm delay. Xzone, COOL, ALARM INPUT 2 TRIPPED 20 s Alarm input 2 Xzone cool has tripped. Check terminal connections 19-20 on I/O-module B. 20 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 8
    “Sensor 3” (the sensor placed on the left-hand side) or “Sensor 4” (the sensor placed on the right-hand side). For GOLD RX the sensor can also be used as a tem- perature alarm and be placed after the supply air fan. 3 second alarm delay.
  • Page 9
    B = B alarm h=hour 10:4 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY COMPENSATION DEFECTIVE (GOLD RX/PX/CX) The temperature sensor in the extract air fan intake cannot establish correct communications or shows an incorrect value. Check that the sensor is connected to the connection on the IQlogic controller.
  • Page 10
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 11
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 12
    20 minutes. Alarm limit 5 K (adjustable). Check the correct function on heat exchangers and any reheaters. Also check that the aforementioned are dimensioned for the current setpoint. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 13
    The heat exchanger’s efficiency is below the preset alarm limit for more than 2 minutes. Check the operation of the heat exchanger. GOLD RX: check that the heat exchanger belts do not slip. GOLD PX: check damper operations so that all dampers and actuators work correctly.
  • Page 14
    The VOC sensor has read a level below or above the set point alarm limit for more than 60 seconds. Factory setting 450 ppm and 10,000 ppm (adjustable). Alarm group 14: Spare www.swegon.com We reserve the right to alter specifications without notice.
  • Page 15
    Check that the function selector switch on the I/O mod- ule is set to position 3 and that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 16
    Check terminal connections 2(Y) and 4(U) on I/O-mod- ule 3. Check that the damper does not seize or that the actua- tor slips on the damper shaft. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 17
    Check that the sensor is connected with the right polar- ity. For pump run at constant speed: Check terminal connections 7-8 on I/O-module 1. Check that the sensor is connected with the right polar- ity. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 18
    The air handling unit’s control unit cannot establish cor- rect communications with the rotary heat exchanger’s motor controller. Check that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 19
    Check the incoming voltage to the air handling unit and the outgoing voltage from the transformer. The voltage must not exceed 36 V +15 %. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 20: Over Temperature

    ALARM LIMIT 5) Heated water temperature exceeds preset set point longer than 30 minutes. Alarm limit 7 K (adjustable). Check the correct function on heating circuit and that the valve functions correctly. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 21
    COOL DX, COMPRESSOR NO. 1 LOW PRESSURE SEN- SOR DEFECTIVE Low pressure sensor is defective or is not connected. Check terminal connections 8 (Black), 15 (Green) and 16 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 22
    COOL DX, COMPRESSOR NO. 2 HIGH PRESSURE SEN- SOR DEFECTIVE High pressure sensor is defective or is not connected. Check terminal connections 2 (Black), 9 (Green) and 10 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 23
    The air handling unit’s control unit cannot establish cor- rect communication with I/O module no. 5, AQUA Link 23:11 AQUA Link, PUMP MONITORING TRIPPED 10 s Pump to AQUA Link is defective. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 24: Communication Error

    27:2 AHU FILTER, SUPPLY AIR FOULED 10 m The pressure across the AHU supply air filter has ex- ceeded the preset alarm limit for more than 10 minutes. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 25
    AIRFLOW MEASUREMENT, PURGING PRESSURE SENSOR 10 s NO. B COMMUNICATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with the sensor of the rotary heat exchanger purging sector. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 26
    , OUTDOOR AIR DAMPER MONITORING TRIPPED 10 m The damper actuator does not move to the right posi- tion. The position-confirming output signal from the damper is not the same as the input control signal. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 27
    A new service period can be set and reset under ALARM SETTINGS. 33:15 LOCK FUNCTION TRIPPED – – – Contact Swegon or their representative. Alarm group 34: External controls 34:1 EXTERNAL CONTROL, I/O MODULE NO. 3 COMMUNI- 10 s CATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with I/O module No.
  • Page 28
    682, 697 563, 578, MIRU NO. 1-3 FLOW BELOW SET POINT ALARM LIMIT 1200 s 40:8 The flow has dropped below its set point for a period longer than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 29
    EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR 10 s 60:1 841, 856, The air handling unit’s control unit cannot establish 871, 886 correct communication with the extract air fan motor controller. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 30
    EXTRACT AIR FAN NO. 1A I/O MODULE COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with extract air fan no. 1A I/O module. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 31
    Phase sequence protection for feed voltage to HC has tripped. 71:1 1051 HC COMPRESSOR MOTOR CONTROL COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with the HC compressor motor control. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 32
    HC pressure equalisation high pressure circuit 1, has tripped. 72:14 1079 HC LOW PRESSURE CIRCUIT 1 BELOW ALARM LIMIT 10 s HC low pressure circuit 1 falls below the set alarm limit. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 33
    1206, SMART LINK NO. 1-4 EVAPORATION TEMPERATURE 30 s 84:6 1221, BELOW ALARM LIMIT 1236, The evaporation temperature drops below the preset 1251 alarm limit for more than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 34
    Stops the AHU if the temperature is below the adjustable limit. Inactive as factory setting. Contact Swegon or their representative. Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU Control 4.
  • Page 35: Information Messages

    ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent at 30 minute intervals. The message is not received after completed heat exchanger calibration. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 36: Calibration Failure

    Temperature sensor for heat-retaining function is not fitted or is not connected correctly. 99:14 INTERNAL SERIAL MEMORY ERROR CPEx1 Internal serial memory error CPEx1 99:15 CLOCK CIRCUIT DEFECTIVE Circuit for the clock is defective www.swegon.com We reserve the right to alter specifications without notice.

Information messages are displayed in the hand-held terminal.

Information messages are displayed only when the terminal is in

the Dashboard image.

Message No.

97:12

97:13

97:14

97:15

98:1

98:2

98:3

98:4

98:5

98:6

98:7

98:8

98:9

98:10

98:11

98:12

98:13

98:14

104

www.swegon.com

Message text

PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION NOT PERFORMED

Bypass optimization of plate heat exchanger cannot be performed.

PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION FAILURE

Bypass optimization of the plate heat exchanger has been performed, but the readings are not

satisfactory.

PLATE HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED

Defrosting calibration of the plate heat exchanger cannot be performed.

PLATE HEAT EXCHANGER DEFROSTING CALIBRATION FAILURE

Defrosting calibration of the plate heat exchanger has been performed, but the readings are not

satisfactory.

SUPPLY AIR PRE-FILTER CALIBRATION NOT PERFORMED

Pre-filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message is

not received after completed filter calibration.

SUPPLY AIR PRE-FILTER CALIBRATION FAILURE

Pre-filter calibration failure, supply air. Recurrent at 5 second intervals.

EXTRACT AIR PRE-FILTER CALIBRATION NOT PERFORMED

Pre-filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message

is not received after completed filter calibration.

EXTRACT AIR PRE-FILTER CALIBRATION FAILURE

Pre-filter calibration failure, extract air. Recurrent at 5 second intervals.

SUPPLY AIR AHU FILTER CALIBRATION NOT PERFORMED

supply air AHU filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals.

The message is not received after completed filter calibration.

SUPPLY AIR AHU FILTER CALIBRATION FAILURE

AHU filter calibration failure, supply air. Recurrent at 5 second intervals.

EXTRACT AIR AHU FILTER CALIBRATION NOT PERFORMED

AHU filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message

is not received after completed filter calibration.

EXTRACT AIR AHU FILTER CALIBRATION FAILURE

AHU filter calibration failure, extract air. Recurrent at 5 second intervals.

SUPPLY AIR END FILTER CALIBRATION NOT PERFORMED

End filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message

is not received after completed filter calibration.

SUPPLY AIR END FILTER CALIBRATION FAILURE

End filter calibration failure, supply air. Recurrent at 5 second intervals.

ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED

Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent

at 30 minute intervals. The message is not received after completed heat exchanger calibration.

ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION FAILURE

Defrost calibration failure, rotary heat exchanger. Recurrent at 5 second intervals.

ReCO

CALIBRATION NOT PERFORMED

2

ReCO

calibration not performed after function was activated for first time. Recurrent at 30 minute intervals.

2

Message is not received after completed ReCO

ReCO

CALIBRATION FAILURE

2

ReCO

calibration failure. Recurrent at 5 second intervals.

2

Information messages provide information e.g. about necessary

settings that have not been entered or unfavourable operating

conditions.The information message is indicated by a blue circle

in the alarm log button on the instrument panel.

calibration.

2

We reserve the right to alter specifications without notice.

GB.GOLDSKE.160901

Swegon GOLD RX: Available Instructions

Important to remember:

Guidesimo.com webproject is not a service center of Swegon trademark and does not carries out works for diagnosis and repair of faulty Swegon GOLD RX equipment. For quality services, please contact an official service center of Swegon company. On our website you can read and download documentation for your Swegon GOLD RX device for free and familiarize yourself with the technical specifications of device.

  • © 2011 ThetfordC260User ManualThetford B.V.Nijverheidsweg 29Postbus 1694870 AD Etten-LeurNederlandT +31 (0)76 5042200F +31 (0)76 5042300E [email protected] Ltd.Unit 19Parkwood Industrial EstateOakham DriveSheffield, S3 9QXEnglandT +44 (0)114 273 8157F +44 (0)114 275 3094E [email protected] GmbHSchallbruch 1442781 HaanDeutschlandT +49 (0)2129 94250F +49 (0)2129 942525E [email protected] …

    C260 Cassette Toilet Toilets, 40

  • Quality Home Appliances EN DE FR IT NL ES SF-5011 FLOOR FAN SF-5011 BODENVENTILATOR SF-5011 VENTILATEUR SANS PIEDS SF-5011 VENTILATORE ORIZZONTALE SF-5011 STAANDE VENTILATOR SF-5011 VENTILADOR DE PISO Instruction for use Gebrauchsanweisung Mode d`emploi Manuale d´ uso Gebruiksaanwijzing Instrucciones de uso SF-5011 EN: For your own safety read these instructions carefull …

    SF-5011 Fan, 19

  • Operating instructionsG2E140-AL40-01Translation of the original operating instructionsCONTENTS1. SAFETY REGULATIONS AND INFORMATION11. SAFETY REGULATIONS AND INFORMATIONRead these operating instructions carefully before starting work on thedevice. Observe the following warnings to prevent malfunctions ordanger to persons.These operating instructions are to be regarded as part of the device.The dev …

    G2E140-AL40-01 Fan, 11

  • YG614-NI120 V~ 60 Hz 80 WModel: 129 825Conner52 in Ceiling FanOwner’s Manual ConnerVentilador de Techo de 1,32 mManual del Propietario Read and follow all the instructions before using this product. …

    Home Decorators Conner Fan, 20

  • Item # 813-677, 813-545, 813-875 Model # 52371, 52372, 52379UL Model # 52-RMGUSE AND CARE GUIDESOUTHWIND 52-INCH CEILING FANQuestions, problems, missing parts? Before returning to the store call Hampton Bay Customer Service8 a.m. — 6 p.m., EST, Monday-Friday1-877-527-0313HAMPTONBAY.COMTHANK YOUWe appreciate the trust and condence you have placed in Hampton Bay through the purchase of this ceil …

    52-RMG Fan, 32

  • INSSBF0708‘‘SBF’’ & “SPBF” series Bathroom fanModels: SBF050 – SBF070 – SBF090 – SBF120 – SPBF050 – SPBF070Before installing and operating this product, the user and/or installer must read, understand and follow these instructions and keep them handy for future reference. If these instructions are not followed, the warranty will be considered null and void and the manufac …

    SBF050 Fan, 4

More Fan Instructions:

  • Bookmarks

Quick Links

MANUAL FOR ALARMS AND INFORMATION MESSAGES

GOLD RX/PX/CX/SD

Generation F

Applicable to Program Version 1.30 and newer versions

loading

Related Manuals for Swegon GOLD RX

Summary of Contents for Swegon GOLD RX

  • Page 1
    MANUAL FOR ALARMS AND INFORMATION MESSAGES GOLD RX/PX/CX/SD Generation F Applicable to Program Version 1.30 and newer versions…
  • Page 2
    GB.GOLDSKFLARM.190920 Content Innehåll 1. Alarm Descriptions with Factory Settings ….. 3 2. Information Messages ………. 35 The document was originally written in Swedish. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 3: Alarm Descriptions With Factory Settings

    3 second alarm delay. PRE-HEAT, VALVE MONITORING TRIPPED 10 m Valve actuator, air heater, water. The valve actuator’s response signal deviates from the outgoing control signal. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 4
    EXTRA REGULATION SEQUENCE 1, TEMPERATURE PRO- TECTION FROM COMMUNICATION ERROR The air handling unit’s control unit does receive the temperature via the external communications interface within the set time limit. 5 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 5: Electrical Heater

    SOR DEFECTIVE Supply flow temperature sensor to the combi coil is defective or not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module F. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 6
    Xzone, SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE Supply air sensor is defective or is not connected. Check terminal connections 9-10 and the sensor’s polar- ity on I/O-module A. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 7: Alarm Limit

    20 second alarm delay. Xzone, COOL, ALARM INPUT 2 TRIPPED 20 s Alarm input 2 Xzone cool has tripped. Check terminal connections 19-20 on I/O-module B. 20 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 8
    “Sensor 3” (the sensor placed on the left-hand side) or “Sensor 4” (the sensor placed on the right-hand side). For GOLD RX the sensor can also be used as a tem- perature alarm and be placed after the supply air fan. 3 second alarm delay.
  • Page 9
    B = B alarm h=hour 10:4 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY COMPENSATION DEFECTIVE (GOLD RX/PX/CX) The temperature sensor in the extract air fan intake cannot establish correct communications or shows an incorrect value. Check that the sensor is connected to the connection on the IQlogic controller.
  • Page 10
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 11
    For several connected sensors: check that the function selector switches are not set in the same position and check that the cables are connected correctly between the sensor and connection unit. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 12
    20 minutes. Alarm limit 5 K (adjustable). Check the correct function on heat exchangers and any reheaters. Also check that the aforementioned are dimensioned for the current setpoint. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 13
    The heat exchanger’s efficiency is below the preset alarm limit for more than 2 minutes. Check the operation of the heat exchanger. GOLD RX: check that the heat exchanger belts do not slip. GOLD PX: check damper operations so that all dampers and actuators work correctly.
  • Page 14
    The VOC sensor has read a level below or above the set point alarm limit for more than 60 seconds. Factory setting 450 ppm and 10,000 ppm (adjustable). Alarm group 14: Spare www.swegon.com We reserve the right to alter specifications without notice.
  • Page 15
    Check that the function selector switch on the I/O mod- ule is set to position 3 and that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 16
    Check terminal connections 2(Y) and 4(U) on I/O-mod- ule 3. Check that the damper does not seize or that the actua- tor slips on the damper shaft. 10 minute alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 17
    Check that the sensor is connected with the right polar- ity. For pump run at constant speed: Check terminal connections 7-8 on I/O-module 1. Check that the sensor is connected with the right polar- ity. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 18
    The air handling unit’s control unit cannot establish cor- rect communications with the rotary heat exchanger’s motor controller. Check that the cable is connected to COM 6-11 on the IQlogic controller. 10 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 19
    Check the incoming voltage to the air handling unit and the outgoing voltage from the transformer. The voltage must not exceed 36 V +15 %. 3 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 20: Over Temperature

    ALARM LIMIT 5) Heated water temperature exceeds preset set point longer than 30 minutes. Alarm limit 7 K (adjustable). Check the correct function on heating circuit and that the valve functions correctly. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 21
    COOL DX, COMPRESSOR NO. 1 LOW PRESSURE SEN- SOR DEFECTIVE Low pressure sensor is defective or is not connected. Check terminal connections 8 (Black), 15 (Green) and 16 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 22
    COOL DX, COMPRESSOR NO. 2 HIGH PRESSURE SEN- SOR DEFECTIVE High pressure sensor is defective or is not connected. Check terminal connections 2 (Black), 9 (Green) and 10 (White) on I/O-module 2. 5 second alarm delay. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 23
    The air handling unit’s control unit cannot establish cor- rect communication with I/O module no. 5, AQUA Link 23:11 AQUA Link, PUMP MONITORING TRIPPED 10 s Pump to AQUA Link is defective. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 24: Communication Error

    27:2 AHU FILTER, SUPPLY AIR FOULED 10 m The pressure across the AHU supply air filter has ex- ceeded the preset alarm limit for more than 10 minutes. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 25
    AIRFLOW MEASUREMENT, PURGING PRESSURE SENSOR 10 s NO. B COMMUNICATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with the sensor of the rotary heat exchanger purging sector. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 26
    , OUTDOOR AIR DAMPER MONITORING TRIPPED 10 m The damper actuator does not move to the right posi- tion. The position-confirming output signal from the damper is not the same as the input control signal. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 27
    A new service period can be set and reset under ALARM SETTINGS. 33:15 LOCK FUNCTION TRIPPED – – – Contact Swegon or their representative. Alarm group 34: External controls 34:1 EXTERNAL CONTROL, I/O MODULE NO. 3 COMMUNI- 10 s CATION ERROR The air handling unit’s control unit cannot establish cor- rect communication with I/O module No.
  • Page 28
    682, 697 563, 578, MIRU NO. 1-3 FLOW BELOW SET POINT ALARM LIMIT 1200 s 40:8 The flow has dropped below its set point for a period longer than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 29
    EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR 10 s 60:1 841, 856, The air handling unit’s control unit cannot establish 871, 886 correct communication with the extract air fan motor controller. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 30
    EXTRACT AIR FAN NO. 1A I/O MODULE COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with extract air fan no. 1A I/O module. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 31
    Phase sequence protection for feed voltage to HC has tripped. 71:1 1051 HC COMPRESSOR MOTOR CONTROL COMMUNICA- 10 s TION ERROR The air handling unit’s control unit cannot establish correct communication with the HC compressor motor control. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 32
    HC pressure equalisation high pressure circuit 1, has tripped. 72:14 1079 HC LOW PRESSURE CIRCUIT 1 BELOW ALARM LIMIT 10 s HC low pressure circuit 1 falls below the set alarm limit. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 33
    1206, SMART LINK NO. 1-4 EVAPORATION TEMPERATURE 30 s 84:6 1221, BELOW ALARM LIMIT 1236, The evaporation temperature drops below the preset 1251 alarm limit for more than 30 seconds. www.swegon.com We reserve the right to alter specifications without notice.
  • Page 34
    Stops the AHU if the temperature is below the adjustable limit. Inactive as factory setting. Contact Swegon or their representative. Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU Control 4.
  • Page 35: Information Messages

    ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent at 30 minute intervals. The message is not received after completed heat exchanger calibration. www.swegon.com We reserve the right to alter specifications without notice.

  • Page 36: Calibration Failure

    Temperature sensor for heat-retaining function is not fitted or is not connected correctly. 99:14 INTERNAL SERIAL MEMORY ERROR CPEx1 Internal serial memory error CPEx1 99:15 CLOCK CIRCUIT DEFECTIVE Circuit for the clock is defective www.swegon.com We reserve the right to alter specifications without notice.

GOLD RX Doc Specifications:

1016/1016246-gold_rx.pdf file (08 Mar 2023)

Accompanying Data:

Swegon GOLD RX Air Conditioner, Air Handlers PDF Operation And Maintenance Instructions (Updated: Wednesday 8th of March 2023 07:36:05 AM)

Rating: 4.9 (rated by 21 users)

Compatible devices: ROE Series, PELICAN Ceiling, CASA W5 Smart, GOLD SD 004/005, PARASOL Z VAV b, PARASOL m X, TBLZ-1-47, ADAPT Extract d.

Recommended Documentation:

Swegon GOLD RX: Text Version of Operation And Maintenance Instructions

(Ocr-Read Summary of Contents of some pages of the Swegon GOLD RX Document (Main Content), UPD: 08 March 2023)

  • 105, GB.GOLDSKE.160901 www.swegon.com 105 We reserve the right to alter specifications without notice. Alarm No. Alarm text Function 98:15 ReCO 2 WRONG SETTING Pressure regulation, slave control or wrong type of AHU is selected. Recurrent at 5 second intervals. 99:1 E-MAIL ERROR Error when sending e-mail…

  • 92, GB.GOLDSKE.160901 92 www.swegon.com We reserve the right to alter specifications without notice. Alarm No. Alarm text Function Priority Stop Delay Resetting 0 = Blocked 0 = In operat. s = second 0 = manual A = A alarm 1 = Stop m = minute 1 = automatic B = B alarm h=hour 11:9 OUTDOOR TEMPERATURE S…

  • 168, Swegon GOLD RX GB.GOLDSKE.160901 168 www.swegon.com We reserve the right to alter specifications without notice. Alarm No. Function Factory-preset valuee Adjusted value Priority Effect Priority Effect 0 = Blocked 0 = In oper. 0 = Blocked 0 = In oper. A = alarm A 1 = Stop A = A alarm 1 = Stop B = B alarm B = B …

  • 54, GB.GOLDSKE.160901 54 www.swegon.com We reserve the right to alter specifi cations without notice. Fire alarms 6.4.8 Alarm settings 6.4.8.1 Fire alarms Internal fi re alarm The air handling unit’s internal temperature sensors serve as fi re protection thermostats. An alarm is initiated if the supply air tem…

  • 191, Swegon GOLD RX GB.GOLDSKE.160901 www.swegon.com 191 We reserve the right to alter specifications without notice. SD, without coil heat exchanger, with filter Thermal efficiency Nominal flow rate Effective electric power SFPint Face velocity Nominal external pressure Internal pressure drop vent. comp. Overall fan…

  • 16, Swegon GOLD RX GB.GOLDSKE.160901 16 www.swegon.com We reserve the right to alter specifications without notice. Airow Status Regulation mode Boost Unit Air adjustments Outdoor air compensation Booster diffusers Operation level Supply air Extract air Unit Remaining time Required time h min. FORCING UNIT AIRFLOW AD…

  • 76, GB.GOLDSKE.160901 76 www.swegon.com We reserve the right to alter specifi cations without notice. 6.4.17 All Year Comfort The All Year Comfort function controls, via control valves, the supply fl ow temperature to the comfort modules, cooling beams, perimeter wall units, etc. The water tempe…

  • Swegon GOLD RX User Manual

  • Swegon GOLD RX User Guide

  • Swegon GOLD RX PDF Manual

  • Swegon GOLD RX Owner’s Manuals

Recommended: WTS950LN, 315.11351, SW

  • Lennox Merit Series

    Page 1INSTALLATIONINSTRUCTIONSML196DFE507968-02Supersedes 507968-01 07/2020THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man-uals, be alert to the potential for personal injury or death. WARNINGImpr …

    Merit Series 50

  • Carrier 39CCN

    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53390017-01 Printed in U.S.A. Form 39CC-1SI Pg 1 1-15 Replaces: NewInstallation, Start-Up and Service InstructionsCONTENTSPageSAFETY CONSIDERATIONS . . . . . …

    39CCN 12

  • York ALL

    Johnson Controls Unitary Products 1060254-UUM-A-0713USER’S INFORMATION MANUALAIR HANDLERSMODELS: ALLISO 9001Certified QualityManagement SystemTABLE OF CONTENTSCONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1HOW YOUR AIR HANDLER WORKS . . . . . . . . . . . . . . …

    ALL 6

Additional Information:

Popular Right Now:

Operating Impressions, Questions and Answers:

GB.XZONE.080630

We reserve the right to alter specifications.

www.swegon.com 1

Function Guide for the GOLD,

Xzone

1. General

The Xzone function is designed for controlling one extra

temperature zone via the ventilation system.

Sometimes it is necessary to control a part of the venti-

lation system with different temperature prerequisites.

This may be due to proximity to the perimeter wall of the

building facing north or south; workshop, office or other

conditions that give rise to different temperature loads in

various parts of a building.

The Xzone function can control one extra temperature

zone, max.

Xzone can be used for all types of GOLD air handling unit

with program version 5.00 or later, and both postheating

and cooling can be controlled in the extra zone.

When Xzone is activated, several menus appear in the

hand-held micro terminal under user level for setting and

reading the extra zone parameters.

The type of temperature control for the extra zone must

be selected separately, and can be of another type than

that used in the main zone.

If extract air temperature control is selected, the tem-

perature sensors must be positioned so that they will not

be influenced by the temperature in the other zone. This

means that the internal extract air sensor (inside the air

handling unit) must not be used for control for the main

zone. The room sensor or extra extract air sensor should

be used, (see TBLZ-1-30 or TBLZ-1-24 in section Material

Specification).

The air heater and air cooler for the main and extra zone

must be sized on the basis of separate computerized

calculations. Always take into account that the duct sys-

tem where the air heater and air cooler are fitted, does

not have the same dimensions as the connection spigots/

frames of the air handling unit.

2. Material Specification

Air handling unit: All types of GOLD

Xzone Control box TBLZ-1-50-a-b-cc

Consists of: IQnomic Plus, TBIQ-2-1, heating

IQnomic Plus, TBIQ-2-1, cooling

Comm. cable BC1-1 (L=250mm)

Code: a 0 = Without freeze protection monitor sensor

1 = With freeze protection monitor sensor

b 1= With supply air temperature sensor

2 = With supply air and extract air temperature

sensor

3 = With supply air and room air temperature

sensor

cc 01 = With 1 metre long communication cable

03 = With 3 metre long communication cable

05 = With 5 metre long communication cable

10 = With 10 metre long communication cable

15 = With 15 metre long communication cable

Supply air temperature sensor, set (TBLZ-1-30), according

to selection above consists of the following:

Duct temperature sensor 32106304

Jack for wall mounting 019611

Extract air temperature sensor, set (TBLZ-1-30), according

to selection above consists of the following:

Duct temperature sensor 32106304

Jack for wall mounting 019611

Room temperature sensor (TBLZ-1-24), according to selec-

tion above.

When the heater is electric of type Swegon standard incl.

control cable:

Adaptor modular/terminal TBLZ-1-55

Возможно, вам также будет интересно:

  • Сват 4 критическая ошибка
  • Сварочный шов полуавтоматом ошибки
  • Сварочный полуавтомат кемпи ошибка 201
  • Сварочный полуавтомат кемпи коды ошибок
  • Сварочный аппарат форсаж 301 коды ошибок

  • Понравилась статья? Поделить с друзьями:
    0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии