Grundfos cu 362 коды ошибок

Code

Description

1

Leakage current

2

Missing phase

3

External fault

Too many pump auto-

4

restarts per 24 h

6

Mains supply fault

Motor-phase sequence

9

reversal

Pump (power line)

10

communication fault

Water-in-oil content too

11

high

Motor operating-time

12

service interval limit

exceeded

15

SCADA callback fault

16

Other fault

Capacity too low

17

(Performance

requirements not met)

Motor protector

18

commanded (test) trip

Diaphragm break — dosing

19

pump

Motor insulation resistance

20

low

Motor max. starts per hour

21

limit exceeded

22

Motor moisture switch

24

Motor/pump vibration high

25

Setup conflict

Load continues despite

26

motor relay is off

Motor protector activated

27

via DI

Change bearings (specific

30

service information)

32

Motor high voltage

33

Soon time for service

Gas in pump head,

35

deaerating problem

36

Pressure valve leakage

37

Suction valve leakage

38

Venting valve defect

18

Origin

Cause

CUE

Leakage current detected

MP

Phase disconnected

204/CUE

MP 204/IO

351/IO

Fault in external module

113/CUE

MP 204

Overcurrent

MP

Phase missing or drifted

204/CUE

MP 204

Phases interchanged

IO 113

Communication to SM 113 Check cables between IO 113 and SM 113.

IO 113

Water-in-oil compartment

CU 362

Service interval

CU 362

SCADA failed to respond

CUE

Fault reported by CUE

Dosing

Dosing volume not met

pump

MP 204

Test trip activated

Dosing

Diaphragm break detected Replace diaphragm in dosing pump.

pump

IO 113/MP

Insulation resistance

204

too low

CU 362

Max. starts exceeded

IO 113

Moisture switch activated

Vibration threshold

IO 113

exceeded

IO 113

Setup conflict in IO 113

Current drawn when it

MP 204

should not be

CU 362

Motor protection tripped

Change bearings reported

CUE

by CUE

MP

Voltage too high

204/CUE

Dosing

Service interval is close

pump

Dosing

Gas in pump head

pump

Dosing

Pressure valve leakage

Pump

Dosing

Suction valve leakage

pump

Dosing

Venting valve defect

pump

Remedy

Check CUE local HMI for fault description.

Check pre-fuses and circuit breakers.

Check all external modules connected via GENIbus.

Check pump, valves and pipes for blockages.

Check voltages between phases, pre-fuses and circuit

breakers.

Check phase sequence.

Water-in-oil content has passed threshold. Lower shaft-

seal and oil needs replacement.

User-defined service interval has been reached.

Arrange for preventive maintenance.

Check cellular network connection. Check if SCADA

phone number is correct. Check status of external

SCADA system.

Check fault locally on CUE drive.

Check status of dosing pump. Perform calibration

of dosing pump.

Test trip activated on MP 204.

Check setting. Motor may need replacement.

User setting of max. number of starts exceeded.

Evaluate setting. Evaluate stop and start levels to

increase pump runtime.

Moisture or water detected inside motor. Overhaul of

pump or motor is needed.

Check pump, valves and pipes for blockages. Pump

may need overhaul.

Check settings of DIP switches of IO 113. Check

warning and alarm threshold in IO 113 by using PC Tool

Water Utility.

Check motor relay (possibility of contact welding).

Check possible causes for tripping. Check pump,

valves and pipes for blockages.

Check local alarms and instructions on CUE.

Voltage on one or multiple phases is too high. Check

incoming voltage.

User-defined service interval is close. Arrange for

preventive maintenance on dosing pump.

Check the installation and operating instructions of

the dosing pump for remedy.

Check the installation and operating instructions of

the dosing pump for remedy.

Check the installation and operating instructions of

the dosing pump for remedy.

Check the installation and operating instructions of

the dosing pump for remedy.

  1. Manuals
  2. Brands
  3. Grundfos Manuals
  4. Measuring Instruments
  5. CU 362

Manuals and User Guides for Grundfos CU 362. We have 2 Grundfos CU 362 manuals available for free PDF download: Installation And Operating Instructions Manual

  • G-858BP Backpack Mag Cesium Vapor Magnetometer Operation Manual COPYRIGHT © DECEMBER 2010 P/N 25271-OM Rev. A GEOMETRICS, INC. 2190 Fortune Drive, San Jose, CA 95131 USA Phone: (408) 954-0522 Fax: (408) 954-0902 …

    G-858BP Measuring Instruments, 108

  •  Turning ___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ …

    SINUMERIK 840D sl Controller, 714

  • PFDWinAIR Compact Differential GaugeInstructions and Maintenance ManualWINTERS INSTRUMENTS Tel: 1-800-WINTERS / www.winters.comDimensions (mm)SpecicationsDial 2 1/16” (52.4mm), white aluminum with black markingsCase Glass lled nylon, blackLens PolycarbonateRing Threaded die-cast black aluminumProcess Connections 3/16″ barbed for ID tubingMovement Resistance-free a …

    WinAIR PFD Series Measuring Instruments, 2

  • Rain Master Irrigation Systems DX2 User Manual Page 232 Appendix A: Flow Meters Appendix A Flow Meters The Evolution DX2 series controller provides a variety of user-configurable, flow-related features for either one or two flow sensors, referred to as Flow #1 and Flow #2. The Evolution DX2 flow features/capabilities include: • Display of instantaneous flow rate in …

    DX2 series Measuring Instruments, 22

  • IInnssttrruuccttiioonn MMaannuuaallMMaannuuaall ddee IInnssttrruucccciioonneessMMaannuueell dd’’IInnssttrruuccttiioonnssMMaannuuaallee ddii IIssttrruuzziioonniiBBeeddiieennuunnggssaannlleeiittuunnggIInnssttrruuççõõeess ddee UUttiilliizzaaççããooModels56-DGT2 56-DGT10Electronic DigitalTransit/TheodoliteINSTRUCTION MANUAL …

    56-DGT2 Measuring Instruments, 92

  • [ https://berlin.museum-digital.de/index.php?t=objekt&oges=47043 (04.02.2021) ]Bedienungsanleitung: Bedienungsanleitung TelefunkenMagnetophon 70Deutsches Technikmuseum- Inv. Nr:I.2.060 P-Tfk 03214Bedienungsanleitung Telefunken Magnetophon 70Telefunken Magnetophon 70Mehrsprachige Bedienungsanleitung f¨ur das Tonbandger¨at Telefunken Mag-netophon 70 mit illustrierter Beschr …

    Magnetophon 70 Measuring Instruments, 10

  • Products Solutions ServicesBrief Operating InstructionsLiquiline Control CDC90Automated cleaning and calibration of MemosenssensorsThese Instructions are Brief Operating Instructions; they arenot a substitute for the Operating Instructions pertaining tothe device.Detailed information on the device can be found in theOperating Instructions and in the other documentationavailable …

    Liquiline Control CDC90 Measuring Instruments, 72

  • 10864EN March 2017Metering systeMsSatellite with electronic regulationge556Y404 (ge556-2 SerieS)047U57228• Self-modulating circulator 15/6, centre distance 130 mm, complying with ErP directive (2009/125/CE).• Heat exchanger and fully insulated piping.• WRAS-certied components for the sanitary circuit.• Spacers for inserting the meters.• Painted sheet metal cabinet …

    GE556-2 Series Measuring Instruments, 6

  • MO25‐EN‐SP‐DE‐FR‐IT‐PTv1.13/14123451234512345MO25MOISTUREMETERUSERGUIDEIntroductionThe MO25 measures moisture (%WME) in wood, brick, concrete,paper,&fabricandtracesleakageinsidewalls,ceilings,andfloors.Descri …

    MO25 Measuring Instruments, 2

  • Instructions050-3635-00Inverter Board and Cable Replacement KitTLA715 and TLA7UPTDS5000, TDS6000, CSA/TDS7000, CSA/TDS8000,TLA600, and VM5000 Series075-0908-00*P075090800*075090800WarningThe servicing instructions are for use by qualifiedpersonnel only. To avoid personal injury, do notperform any servicing unless you are qualified todo so. Refer to all safety summaries prior to …

    TLA715 Series Inverter, 10

  • NOYAFA

    NF-820

    Anti-jamming underground cable detectorVER: V4NF-820Your excellent helper in cable test!ORIGINAL AUTHENTICed produntctetsa,Ping noteit arfltelonwueodCORIGINAL AUTHENTICYour excellent helper in cable test!INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL …

    NF-820 Measuring Instruments, 7

  • VOLTCRAFT

    DT-30LK

    BedienungsanleitungDT-30LK DrehzahlmesserBest.-Nr. 1012206Seite 2 — 16Operating InstructionsDT-30LK TachometerItem No. 1012206 Page 17-31Mode d’emploiDT-30LK Compte Tours/MinNº de commande 1012206 Page 32-46GebruiksaanwijzingDT-30LK ToerentalmeterBestelnr. 1012206 Pagina 47-63 …

    DT-30LK Measuring Instruments, 64

  • Kusam-meco

    KM 3060

    G-17, Bharat Industrial Estate, T. J. Road, Sewree (W), Mumbai — 400 015. INDIA.Sales Direct.: 022-24156638, Tel. : 022-24124540, 24181649, Fax : 022-24149659Email : [email protected], Website : www.kusamelectrical.comAll Specifications are subject to change without prior noticeGENERAL SPECIFICATIONS :AC Current : 0.01A ~ 1000AAC Voltage : 1V ~ 75 …

    KM 3060 Measuring Instruments, 7

Recommended Documentation:

Возможно, вам также будет интересно:

  • Grundfos control lc 221 ошибка f 117
  • Grub probe ошибка не удалось найти привод grub для dev sdb1 проверьте device map
  • Grub install ошибка не удалось получить канонический путь overlay
  • Grub install ошибка не удалось получить канонический путь cow
  • Grub install ошибка не удалось найти каталог efi

  • Понравилась статья? Поделить с друзьями:
    0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии